Traditional Wired & Fire-Rated Glass
Traditional Wired & Fire-Rated Glass
Clear and textured traditional wired glass in square or diamond mesh, with nominal 6 mm, 6.8 mm and 7 mm options. Fire and impact performance must be confirmed for the selected glass and glazing system.
Traditional wired glass: clear and textured finishes
Traditional wired glass contains a metal wire mesh embedded within a single glass pane during forming. Its visible square or diamond pattern gives it a distinctive industrial character, making it an option for matching traditional glazing and creating decorative features. It is different from laminated decorative mesh glass, where a mesh insert is enclosed between separate glass layers.
Thicknesses, textures and mesh patterns
The reference range includes the following nominal options. Thickness, mesh pitch, available sheet size and suitability are confirmed for the selected product before ordering. Please approve a physical sample when matching existing glass.
| Finish | Wire pattern | Nominal thickness | Mesh detail |
|---|---|---|---|
| Pear-pattern textured / obscure | Diamond | 7 mm | Confirm with the selected sample |
| Pear-pattern textured / obscure | Square | 6 mm | Confirm with the selected sample |
| Clear | Square | 6.8 mm | Reference sample: approximately 13 × 13 mm |
| Clear | Diamond | 6.8 mm | Reference sample: approximately 20 × 20 mm mesh |
Clear finishes allow a view through the glass while keeping the wire pattern visible. Textured finishes diffuse light and obscure the view. Mesh dimensions describe the reference samples, not a manufacturing tolerance; wire alignment, texture and dimensions should be checked against the approved sample and order specification.
Fire-rated applications in the UK
A wire mesh does not, on its own, make glass fire-rated or impact-safe. Decorative wired products and tested fire-resistant wired products must be specified separately. The thicknesses and patterns listed above are appearance and dimensional options, not evidence of a fire rating.
Where fire resistance is required, provide the required classification and duration. E refers to integrity, EW adds a radiation limit, and EI includes thermal insulation. An integrity-only product must not be substituted where an insulating classification is required. Any claimed performance must be supported by the relevant test and classification documentation for the exact glass and glazing system.
The frame, beads, seals, fixings, glass size and installation must match the applicable tested or assessed system. We do not assign a blanket 30-, 60- or 90-minute fire rating to these pictured samples.
For doors, low-level glazing and other impact-risk locations, confirm the required BS EN 12600 impact classification separately. Ordinary wired glass should not be assumed to be toughened or laminated safety glass, or described as explosion-proof.
Made-to-measure supply and replacement glazing
Send your panel dimensions, quantity, preferred clear or textured finish, mesh pattern and delivery postcode. For replacement work, include photographs of the existing pane and frame, the measured thickness and any original product markings. Where a fire rating is needed, include the door or screen system details and the project’s required performance.
We focus on product supply and can coordinate with your local installer. The agreed quotation will identify the proposed glass specification and any available supporting performance documentation.
Request a wired-glass quotation
Wired glass sample gallery
Recreated images illustrate mesh patterns and surface finishes. Please use an approved physical sample and the agreed specification for final selection.